In partnership with

Arnold Schwarzenegger has a newsletter.

Yeah. That Arnold Schwarzenegger.

So do Codie Sanchez, Scott Galloway, Colin & Samir, Shaan Puri, and Jay Shetty. And none of them are doing it for fun. They're doing it because a list you own compounds in ways that social media never will.

beehiiv is where they built it. You can start yours for 30% off your first 3 months with code PLATFORM30. Start building today.

Solar Cable Sizing — How to Select the Right Wire for Your PV System

Cable sizing is one of the most commonly cut-corner areas in Philippine solar installations. Installers use undersized cables to reduce material cost — the result is overheating, voltage drop, reduced efficiency, and in worst cases, electrical fires.

Two Criteria for Cable Sizing

Every solar cable must satisfy both of these:

  1. Ampacity — the cable must carry the maximum current without overheating

  2. Voltage drop — the cable must not drop more than 2-3% of system voltage

DC String Cable (Panel to Inverter)

Step 1: Determine Maximum Current

The maximum DC current per string = panel Isc × 1.25 (safety factor per PEC)

Example: JA Solar 550W panel, Isc = 13.83A

Design current = 13.83 × 1.25 = 17.3A

Step 2: Select Cable Size

Cross-section

Ampacity (outdoor, 40°C)

Common Application

2.5 mm²

~20A

Short runs (<10m), low-current strings

4 mm²

~27A

Standard residential DC string cable

6 mm²

~34A

Long runs (>20m) or parallel strings

10 mm²

~46A

Main DC trunk cable in commercial systems

For most 5-10kW Philippine residential systems, 4 mm² solar DC cable is standard.

Step 3: Check Voltage Drop

Voltage Drop = (2 × Length × Current × Resistivity) ÷ Cross-section

Where resistivity of copper = 0.0172 Ω·mm²/m

Example: 4mm² cable, 15m run, 13.83A current:

VD = (2 × 15 × 13.83 × 0.0172) ÷ 4 = 1.78V

As percentage of 345V string voltage: 1.78 ÷ 345 = 0.52% — acceptable (under 2%)

AC Output Cable (Inverter to Distribution Board)

Inverter Size

AC Output Current

Recommended Cable

3 kW

~13.6A @ 220V

3.5mm² THHN

5 kW

~22.7A @ 220V

5.5mm² THHN

8 kW

~36.4A @ 220V

8mm² THHN

10 kW

~45.5A @ 220V

14mm² THHN

Cable Type Requirements

  • DC string cables — must be USE-2 or PV Wire rated (UV resistant, double insulation, rated for 90°C, listed for direct burial and outdoor use). Standard THHN is NOT acceptable for DC outdoor runs.

  • AC output cable — THHN/THWN is acceptable inside conduit. For any exposed outdoor AC run, use THWN-2 (wet location rated).

  • Cable color coding (PEC standard): DC positive = red, DC negative = black, AC live = black, AC neutral = white, ground = green or bare

The Real-World Cost of Undersizing

A 2.5mm² cable instead of 4mm² on a 15m string run in a 5kW system causes approximately 2.1% extra voltage drop. Over a 25-year system life, that's ₱15,000–₱25,000 in lost production for a one-time material saving of about ₱800. It's never worth it.

Engr. Jason Morales — Founder, SolarEnergyPH

Keep Reading