AS 4777.3-2005

Grid Protection Settings — Why They Must Be Correct

Grid protection settings in a solar inverter are the last line of defence against islanding and against the inverter feeding current into a grid that is operating outside safe parameters. If the settings are wrong — too wide (insensitive), the inverter may operate when it should have tripped; too narrow (over-sensitive), the inverter may nuisance trip on normal voltage variations, causing unnecessary export loss.

AS 4777.3 Base Protection Settings

Protection Function

Setting (Vnom = 230 V)

Time Delay

Under-voltage Stage 1 (V<)

207 V (0.90 pu)

2.0 s

Under-voltage Stage 2 (V<<)

184 V (0.80 pu)

0.2 s

Over-voltage Stage 1 (V>)

253 V (1.10 pu)

2.0 s

Over-voltage Stage 2 (V>>)

265 V (1.15 pu)

0.1 s

Under-frequency (F<)

47 Hz

1.0 s

Over-frequency (F>)

52 Hz

1.0 s

DNSP-Specific Adjustments

Individual DNSPs may require tighter settings than the AS 4777.3 base settings. For example, networks with high solar penetration may require Stage 1 over-voltage to be set at 244 V (1.06 pu) rather than 253 V. These settings must be:

  • Confirmed in the DNSP's network connection requirements document (publicly available on the DNSP's website)

  • Configured in the inverter at commissioning using the inverter's protected settings menu (requires an installer access code)

  • Verified using a protection relay test set or by monitoring the inverter's response to simulated out-of-range voltage conditions

  • Recorded on the commissioning form — inverter serial number, date, and settings applied

Engr. Jason Morales — Founder, SolarEnergyPH