In partnership with

The ones showing up in LLMs convert 3× better than Google

They optimized for LLMs, not just Google.

FAQs. Comparison pages. Transparent pricing. LinkedIn presence. These aren't vanity plays. They're what gets you cited in ChatGPT, Gemini, and Claude when your buyers are researching, your investors are looking, and your future hires are deciding where to work.

Download the free AEO Playbook for Startups from HubSpot and get the exact checklist. Five minutes to read.

AS 4777.2-2015

Why Export Limits Exist

Distribution networks were designed to carry power in one direction — from the substation to homes. When many homes export solar simultaneously, the local feeder can become overloaded, causing voltage rise, thermal limits on cables, and protection relay coordination issues. Network distributors respond by limiting how much individual systems can export.

Types of Export Limiting

Type

Description

Equipment Required

Zero export (No export)

Inverter is configured to produce only as much power as the site's own load consumes — no grid export at all

Current transformer (CT) on main switchboard + inverter CT input

Fixed export limit

Inverter caps its output at a set export level regardless of solar production

CT monitoring + inverter power management

Dynamic export limit

Inverter adjusts export in real time based on available feeder capacity — DNSP sends a signal via smart meter or internet

CT + internet-connected inverter + DNSP DER register

How Zero-Export Is Configured

Zero-export installations use a current transformer (CT) clipped around the main supply cable at the switchboard. The CT sends a 4–20 mA or Modbus signal to the inverter indicating how much power the site is currently importing. The inverter's "export power limit" function modulates output to keep the import reading at zero — meaning it matches the site load exactly.

Critical configuration points:

  • CT must be on the grid side of the main switchboard — not the solar AC output side

  • CT polarity must be correct — reversed CT causes the inverter to ramp up when it should ramp down

  • Response speed must be set for the fastest allowable oscillation — too slow causes momentary export; too fast causes instability

  • A 10–50 W export allowance (not true zero) is recommended to avoid the inverter hunting continuously at the setpoint

Dynamic Export — The Future of Network Integration

Several Australian DNSPs (Energex, Western Power, AusNet) are now implementing dynamic export limiting via AS 4777.2's flexible export function. Systems registered in the DNSP's Distributed Energy Resources (DER) register can have their export limit changed remotely — increased during off-peak, reduced during network stress. This allows more solar to be connected to constrained feeders while managing peak export.

Engr. Jason Morales — Founder, SolarEnergyPH


Installation and safety requirements for PV arrays (AS 5033-2014) & Guide to solar safe installation
Installation and safety requirements for PV arrays (AS 5033-2014) & Guide to solar safe installation
A two-in-one reference covering PV array installation and safety requirements per AS 5033-2014, bundled with a practical safe solar installation guide — essential reading for solar installers, elec...
$9.99 usd

Philippines Solar PV Installation Guide 2026 — Based on Australian Standards
Philippines Solar PV Installation Guide 2026 — Based on Australian Standards
A complete technical reference for solar PV system installation in the Philippines — drawn directly from AS/NZS 4509.1:2009, AS 4777.1:2005, and AS/NZS 3000:2007, cross-referenced to PEC 2017 and D...
$9.99 usd