AS/NZS 3000-2018

Earth Leakage in Solar Systems — Three Protection Approaches

Earth leakage protection in a solar installation must address both the AC side (post-inverter) and the DC side (array to inverter). These two circuits require different protection approaches because standard AC RCDs cannot detect DC leakage.

AC Side — RCD/RCBO (Type A minimum)

The AC circuit from inverter to switchboard is protected by a Type A RCD or RCBO rated at 30 mA. This protects against:

  • Insulation breakdown in the AC cable run

  • Touch current from exposed inverter terminals

  • Ground faults in the inverter's AC output circuit

DC Side — Ground Fault Detection (Inverter-Integrated)

Transformerless inverters have a built-in Ground Fault Detection (GFD) circuit that monitors leakage current between the floating DC circuit and the earthed inverter chassis. This provides equivalent protection to an RCD but works in the DC domain. The inverter will shut down and display a fault code if DC leakage exceeds approximately 300 mA.

Isolation Transformer Systems — IMDs

Where the installer specifies an isolation transformer between the solar array and inverter (rare in residential; more common in commercial systems with galvanic isolation requirements), the DC side of the transformer is unearthed. An Insulation Monitoring Device (IMD) must be installed on the DC side to detect the first earth fault before it becomes a double-fault hazard.

Protection Device

Circuit

Trip Threshold

Reset

Type A RCD

AC solar circuit

30 mA

Manual (trip button)

Inverter GFD

DC array

~300 mA

Manual reset on inverter after fault cleared

IMD (isolated DC)

DC side of isolation transformer

Typically 1–10 kΩ to earth

Alarm — may be manual or automatic

Engr. Jason Morales — Founder, SolarEnergyPH

Installation and safety requirements for PV arrays (AS 5033-2014) & Guide to solar safe installation
Installation and safety requirements for PV arrays (AS 5033-2014) & Guide to solar safe installation
A two-in-one reference covering PV array installation and safety requirements per AS 5033-2014, bundled with a practical safe solar installation guide — essential reading for solar installers, elec...
$9.99 usd

Philippines Solar PV Installation Guide 2026 — Based on Australian Standards
Philippines Solar PV Installation Guide 2026 — Based on Australian Standards
A complete technical reference for solar PV system installation in the Philippines — drawn directly from AS/NZS 4509.1:2009, AS 4777.1:2005, and AS/NZS 3000:2007, cross-referenced to PEC 2017 and D...
$9.99 usd